Generator for a well pump: size it from the motor, not a guess

By the Plain Prepper editors. Updated 2026-10-15.

We research products from makers' specs, manuals and safety agencies; we do not run hands-on tests. Links to Amazon may earn us a commission at no cost to you. How this works.

Quick answer

Start with the pump motor's horsepower and whether it is a 2-wire or 3-wire motor. Franklin Electric, which makes submersible well motors, lists a minimum generator rating of 4 kW for a 1 HP 3-wire motor and 6 kW for a 1 HP 2-wire motor. If your pump runs on 240 V, the generator needs a 120/240 V outlet. Franklin also says a transfer switch must be used whenever a generator backs up a home's power lines; have a licensed electrician install it.

Franklin Electric's minimum generator sizes

Franklin Electric's application manual lists the smallest generator it considers adequate for its single-phase submersible motors:

Motor3-wire motor2-wire motor
1/2 HP2 kW3 kW
3/4 HP3 kW4.5 kW
1 HP4 kW6 kW
1.5 HP5 kW7.5 kW
2 HP7.5 kWNot listed
3 HP10 kWNot listed

These are minimums for the pump alone. Anything else you run at the same time, such as a refrigerator or lights, adds to the total. Franklin's reason for the margin: a generator must hold at least 65% of the motor's nameplate voltage while it starts, or the motor may not get enough starting torque.

Find your pump's numbers first

Two generators compared against the table

SpecChampion 201277Champion 201302
Running watts, gasoline7,5009,200
Running watts, propane6,7508,280
Starting watts, gasoline9,37511,500
240 V outletsL14-30RL14-30R and 14-50R
Weight205 lb209 lb

Against Franklin's minimums, both cover a 1 HP 2-wire pump (6 kW) on either fuel. A 1.5 HP 2-wire or 2 HP 3-wire pump (7.5 kW) uses the 201277's entire gasoline running rating with nothing left over, while the 201302 leaves about 1,700 W of running headroom on gasoline.

Connecting it: transfer switch, not a backfeed

Franklin Electric says automatic or manual transfer switches must be used any time a generator is used as standby or backup on power lines, to prevent accidental electrocution, and to contact the power company for use and approval. NFPA also calls for a properly rated transfer switch.

See our transfer switch for portable generator guide for switch types.

Running the pump on a generator

  1. Start the generator first, then turn on the pump circuit. Franklin says to always start the generator before the motor.
  2. Shut the pump off first, then the generator. Franklin warns the motor's thrust bearing can be damaged if the generator coasts down with the motor running or runs out of fuel.
  3. Keep fuel up so the generator never dies under the pump's load.
  4. No reduced voltage starter with a minimum-sized generator; Franklin says the combination can cause motor damage from low voltage.
  5. Frequency matters: Franklin notes a pump running 1 to 2 Hz below its design will not meet its performance curve, and 1 to 2 Hz above may trip overloads.

NFPA says to run portable generators outdoors, at least 20 feet from windows, doors and vent openings.

What to look for when you buy

Covers most 1 HP pumps: Champion 201277 Dual Fuel

Best for: Homes with a 1 HP or smaller pump plus a few essentials

Champion's manual lists 7,500 running watts on gasoline and 6,750 on propane, 120/240 V output and an L14-30R outlet for a 30 amp transfer switch.

Watch out: At 7.5 kW running on gasoline it only just meets Franklin's minimum for a 1.5 HP 2-wire or 2 HP 3-wire motor, with nothing to spare.

See options on Amazon (opens Amazon in a new tab)

More headroom: Champion 201302 Dual Fuel

Best for: Larger pumps or running the pump with other household loads

Champion lists 9,200 running watts on gasoline and 8,280 on propane, L14-30R and 14-50R 240 V outlets, CO Shield shutoff, and 10 hours at half load on a full 7.7 gallon tank.

Watch out: At 209 lb it is heavy to move; propane runtime at half load is 5 hours.

See options on Amazon (opens Amazon in a new tab)

The connection: Connecticut Electric EmerGen 30 A 10-circuit kit

Best for: Feeding a hard-wired pump circuit through a transfer switch

Connecticut Electric's manual lists 30 amp models made for generators with an L14-30 outlet, with a power inlet and cord set.

Watch out: Requires installation by a licensed electrician or qualified professional under local code.

See options on Amazon (opens Amazon in a new tab)

Questions people ask

What size generator do I need for a 1 HP well pump?
Franklin Electric lists a minimum of 4 kW for a 1 HP 3-wire motor and 6 kW for a 1 HP 2-wire motor, before other loads.
Can I plug a well pump into a generator?
Not safely by improvising; Franklin says a transfer switch must be used when a generator backs up power lines, installed by an electrician.
Will a 7,500 watt generator run a well pump?
For most pumps up to 1 HP 2-wire or 2 HP 3-wire, it meets Franklin's minimums, though the larger sizes leave no margin for other loads.
Why does my pump need such a large generator?
Franklin says the generator must hold at least 65% of the motor's nameplate voltage while it starts, so it needs capacity well above running watts.